Plant Controller: PF1
Following checks and corrections are applied during Validation and AutoCorrection.
-
If VREFmax < VREFmin then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If VADJ > VREFmax, then VREFmax = VADJ limits or if VADJ < VREFmin, then VREFmin = VADJ
Model Equations and/or Block Diagrams
Parameters:
| VADJF | Voltage adjuster bypass of pulse generator, 0 inactive, 1 active |
| Tslew | Voltage adjuster travel time, sec. |
| VREFmax | Voltage adjuster maximum output, pu |
| VREFmin | Voltage adjuster minimum output, pu |
| Ton | Voltage adjuster pulse generator time on, sec. |
| Toff | Voltage adjuster pulse generator time off, sec. |
| PFREFnorm | Power factor controller normalized reference setpoint, pu |
| VITmin | Power factor controller minimum terminal current limit, pu |
| VVTmin | Power factor controller minimum terminal voltage limit, pu |
| VVTmax | Power factor controller maximum terminal voltage limit, pu |
| VPFC_BW | Power factor controller deadband magnitude, pu |
| TPFC | Power factor controller delay time, sec. |